Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17 97
7 Commissioning of the system
7.3 Detailed description of the commissioning steps
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7.3.14.2 Configuring individual PDO mapping
In addition to the static and preconfigured PDO mappings, you can also configure an individual PDO
mapping.
How to configure an individual PDO mapping in »PLC Designer«
(example of an individual output PDO for the i700 servo inverter)
1. Open the Process data tab and set a checkmark in the checkbox of the free PDO mapping
(16#1605).