13 Parameter reference
196 Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
13 Parameter reference
This chapter complements the parameter list of the online help for the Lenze Controller by the
parameters of the EtherCAT communication interface.
These parameters ...
are for instance shown in the Lenze »WebConfig« (Engineering tool for web-based
parameterisation);
are listed in numerically ascending order.
C280/4
C281/2
Parameter | Name:
C280/4 | ECAT bus scan compliance
Data type: UNSIGNED_8
Index: 24295.4 =
0x5EE7.0x04
Brief information on whether the master configuration corresponds to the physical bus structure. The master
configuration of the stack is compared to the actual bus structure.
Selection list (Lenze setting printed in bold) Info
0No match The master configuration does not correspond to the bus
structure.
1 OK The master configuration corresponds to the bus
structure.
Read access Write access CINH PLC-STOP No transfer
Parameter | Name:
C281/2 | ECAT master: State
Data type: UNSIGNED_8
Index: 24294.2 =
0x5EE6.0x02
Display of the current master state
Selection list(read only)
0 Unknown
1 Init
2 Pre-operational
3 Bootstrap Mode Bootstrap mode is not supported.
4 Safe-operational
8 Operational
Read access Write access CINH PLC-STOP No transfer