Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17 55
7 Commissioning of the system
7.3 Detailed description of the commissioning steps
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
2. Select Control method (0x2C00 / 0x3400):
Servo control for synchronous motor (SM)
Servo control for asynchronous motor (ASM)
VFC: V/f characteristic control
3. If you do not
obtain the motor data from the catalog, you have to set the moment of
inertia (0x2910/1 / 0x3110/1) to a non-zero value.
The controller parameters are calculated automatically.
4. You can select the parameters for the monitoring functions in the Monitoring settings
section.