Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17 75
7 Commissioning of the system
7.3 Detailed description of the commissioning steps
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7.3.8 Determining the physical EtherCAT configuration (fieldbus scan)
In order to check the physical EtherCAT configuration, you can use »PLC Designer« to carry out a
fieldbus scan on the Lenze Controller online.
Preconditions
In order to execute a fieldbus scan, you must first configure the ...
Configuring the communication parameters
( 73) and ...
then use the menu command Online Login or <Alt>+<F8> to log in on the Lenze Controller.
For this, the PLC program must be error-free.
By means of the log-in, the PLC program is loaded into the controller. In doing so, any existing
program is overwritten.
How to carry out a fieldbus scan with »PLC Designer«
1. Execute the Scan For Devices command in the context menu of the EtherCAT master.
Vue de la page 74