Control technology | EtherCAT communication manual
Commissioning of the system
Detailed commissioning steps
7.2.4.2 Fieldbus scan with the »scandf« command line tool
Fieldbus scanning command
Command: scanfd <interface> /option
The interface for the EtherCAT slaves to be scanned on the fieldbus is called ECAT.
How to carry out a fieldbus scan:
1. Establish a Telnet connection to the IPC.
More detailed information is provided in the documentation for the IPC.
2. Call scanfd.exe via the command line box of the IPC to scan the fieldbus.
3. Determine the available interfaces of the IPC:
Enter scanfd /i.
Output example:
The fieldbus scanner displays the available interfaces:
ECAT for the EtherCAT-capable field devices,
CAN1 and CAN2 for the CAN field devices.
Option Output on the console
/i Determine available interfaces
/t Display device information for every network node.
/f Display additional device parameters for every device if available.
/n Suppress prompt before execution of the fieldbus scan.