DMS 3.1 EN 01/2011 TD17 L 151
Control technology | EtherCAT communication manual
Diagnostics
Error scenarios
11.6.8 Logbook message: "Cannot spawn Remote API Server"
The remote API server enables the access from an engineering tool (e.g. the »Engineer«)
which superimposes the IPC to an EtherCAT slave parameter. The access is made via CoE
(CANopen over EtherCAT).
...
xxxxx DD-MM-YYYY hh:mm:ss
EtherCAT Master Stack
CTRL: Cannot spawn Remote API Server Communication on bus
systems
Error
...
Causes Remedies
No master configuration or a master configuration not
matching the physical bus has been loaded on the
control system. SDO communication with the slave field
devices is not possible.
Create a master configuration with the »EtherCAT
Configurator« and load it onto the control system.
Load the current master configuration onto the
control system.