Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37 Manuel d'utilisateur Page 592

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 679
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 591
9400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00597
592 Firmware 1.37 - 09/2006 L
C00597
C00598
C00599
C00600
Parameter | Name:
C00597 | Resp. to motor phase failure
Data type: UNSIGNED_32
Index: 23978
d
= 5DAA
h
Response to release of motor phase failure monitoring
Selection list
(Lenze setting printed in bold)
0 No response
1 Error
2Trouble
3 Quick stop by trouble
4 Warning locked
5 Warning
; Read access ; Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00598 | Resp. to open circuit AIN1
Data type: UNSIGNED_32
Index: 23977
d
= 5DA9
h
Response if with master current at AIN1 and mode LifeZero (±4...±20 mA) the current is in the non permitted range
(-4...+4 mA).
Selection list
(Lenze setting printed in bold)
0 No response
1 Error
2Trouble
3 Quick stop by trouble
4 Warning locked
5 Warning
6 Information
; Read access ; Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00599 | Threshold motor phase failure
Data type: INTEGER_32
Index: 23976
d
= 5DA8
h
Threshold for motor phase failure monitoring
The response when reaching the threshold can be selected in C00597
.
Setting range
(min. value | unit | max. value) Lenze setting
1.0 % 10.0 5.0 %
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 10
Parameter | Name:
C00600 | Resp. to DC bus overvoltage
Data type: UNSIGNED_32
Index: 23975
d
= 5DA7
h
Response to DC bus overvoltage
Selection list
(Lenze setting printed in bold)
1 Error
2Fault
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT
Vue de la page 591
1 2 ... 587 588 589 590 591 592 593 594 595 596 597 ... 678 679

Commentaires sur ces manuels

Pas de commentaire