Lenze 8400 Manuel d'utilisateur Page 247

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 304
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 246
Commissioning
Quick commissioning
Terminal control
7
247
EDS84ASC552 EN 9.1
7.2.2 Terminal control
Commissioning steps
1. Wiring of power terminals
Make use of the Mounting Instructions supplied with the frequency inverter to wire the
power terminals according to the requirements of your device.
2. Wiring of control terminals.
StateLine
Analog inputs at X3 Assignment Terminal control
X3
O1U
GA
A1I
A1U
AR
1k
...
10k
W
W
0...10 V
"
A1U Setpoint selection
10 V (=100 %):
1500 min
-1
(with 4-pole motor)
Wiring of the digital inputs at X4 Assignment Terminal control
24E
DI1
DI2
DI3
DI4
RFR
X4
DO1
GIO
24I
+
_
DC 24 V
RFR Controller enable: RFR = High
Reset error:
High Low (edge-controlled)
DI1 Fixed frequency 1 ... fixed frequency 3, see
table below
DI2
DI3 DCB
DI1 ... DI4: all active = High DI4 Direction of rotation left/right (CCW/CW)
HighLine/TopLine
Analog inputs at X3 Assignment Terminal control
"
X3
A2I
O2I
A2U
O2U
A1IO1I
A1UO1U
ARGA
1k
10k
...
W
W
0 ... 10V
A1U Setpoint selection
10 V (=100 %):
1500 min
-1
(with 4-pole motor)
Wiring of the digital inputs at X5 Assignment Terminal control
24EDI1
DI2
DI3
DI4 RFR
DC 24 V
X5
DI5DI6
DI7
GI
24I
RFR Controller enable: RFR = High
Reset error:
High Low (edge-controlled)
DI1 Fixed frequency 1 ... fixed frequency 3, see
table below
DI2
DI3 DCB
DI1 ... DI4: all active = High DI4 Direction of rotation left/right (CCW/CW)
3. If you can be sure that the frequency inverter is in the default state (Lenze setting),
you can skip the following step. If not, establish the Lenze setting of the frequency
inverter. We recommend to use the keypad for this.
Vue de la page 246
1 2 ... 242 243 244 245 246 247 248 249 250 251 252 ... 303 304

Commentaires sur ces manuels

Pas de commentaire