Lenze 8400 Manuel d'utilisateur Page 170

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 304
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 169
Electrical installation
Installation according to EMC (installation of a CE-typical drive system)
Control cables
6
170
EDS84ASC552 EN 9.1
6.2.4 Control cables
ƒ Control cables must be shielded to minimise i nterference injections.
ƒ For l engths of approx. 5 m and more, use only shielded cables for analog and digital
inputs and outputs. Under 5 m, unshielded but twisted cables may be used.
ƒ Connect the shield correctly:
The shield connections of the control cables must be at a distance of at least 50
mm from the shield connections of the motor cables and DC cables.
Connect the shield of digital input and output cables at both ends.
Connect the shield of analog input and output cables at one end (at the drive
controller).
ƒ To achieve an optimum shielding effect (in case of very long cables, with high
interference) one shield end of analog input and output c ables can be connected to
PE potential via a capacitor (e.g. 10 nF/250 V) (see sketch).
9300vec043
Fig. 6-4 Shielding of long, analog control cables
Vue de la page 169
1 2 ... 165 166 167 168 169 170 171 172 173 174 175 ... 303 304

Commentaires sur ces manuels

Pas de commentaire