Electrical installation
Devices i n the power range 0.37 ... 22 kW (3/PE AC 400 V)
Terminal assignment of the power connections
6
191
EDS84ASC552 EN 9.1
Strip cables
X105 X106
84MOTL001_a 84MOTL001_b
U, V, W PE T1, T2
b c e a d f g h
[mm] [mm] [mm]
E84AVxxx3714
E84AVxxx5514
E84AVxxx7514
E84AVxxx1124
E84AVxxx1524
E84AVxxx2224
E84AVxxx3024xxS
30
65 7 90 9 95 30 10
E84AVxxx3024xx0
E84AVxxx4024
E84AVxxx5524
25 70 12 ... 14 125 12 ... 14 105 25 10
E84AVxxx7524
E84AVxxx1134
E84AVxxx1534
25 80 14 120 14 115 25 10
E84AVxxx1834
E84AVxxx2234
30 110 16 195 16 160 30 10
How to proceed:
1. Strip motor cable and cable for motor temperature monitoring according to
specified dimensions.
2. Fold back the shield of the motor cable and motor temperature cable over the cable
sheath. Keep unshielded ends short.
3. Fix shield on the cable sheath (e.g. using a heat-shrinkable tube).
4. Fasten wire end ferrule to PE cable.
The other cables may be wired without using wire end ferrules.
5. Connect the shields separately to the shield sheet using (metal) cable ties or shield
clamps.
left: motor cable
right: cable of motor temperature monitoring
For strain relief of the cables, measures are required.