Mechanical installation
Standard devices in t he power range 3 ... 22 kW
Mounting i n ”cold plate” technique
5
129
EDS84ASC552 EN 9.1
5.3.3 Mounting in ”cold plate” technique
The E84AVxxC... controllers are designed for assembly on coolers (e.g. collective coolers) in
”cold-plate” technique.
Requirements for collective coolers
A good thermal connection to the cooler is important for the trouble-free operation of
the c ontroller:
ƒ The c ontact area between the collective cooler and the controller
– must be at least as big as the cooling plate of the controller.
– must be smooth, the maximum deviation must not exceed 0.05 mm.
ƒ The c ollective cooler must be connected to the controller with all required screwed
joints.
ƒ The thermal resistance R
th
must be observed, s ee table.
The values in t he table apply to the operation of the controllers under rated
conditions.
The values include the heat transmission between the cooler and the device.
With a standard heat conducting paste and a film thickness of 50 m, the heat
transmission is approx.
– 0.03 K/W for controllers up to 5.5 kW
– 0.02 K/W for controllers up to 15 kW
– 0.01 K/W for controllers up to 22 kW.
Power to be dissipated Thermal resistance
Type P
v[W]
R
th
[K/W]
E84AVxxC3024xx0 115 0.33
E84AVxxC4024 155 0.25
E84AVxxC5524 215 0.18
E84AVxxC7524 250 0.15
E84AVxxC1134 355 0.11
E84AVxxC1534 390 0.10
E84AVxxC1834 460 0.057
E84AVxxC2234 540 0.057
Ambient conditions
ƒ The rated data and the derating factors at increased temperature also apply to the
ambient temperature of the drive controllers.
ƒ Temperature at the cooling plate of the drive controller: max. 75 °C.
Note!
Apply s tandard heat-conducting paste or heat-conducting foil onto cooler and
cooling plate before you bolt the controller onto the cooler.