Lenze E94AxHE Technology Application CiA402 Device profi Manuel d'utilisateur Page 182

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 232
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 181
9400 Technology applications | CiA402 device profile
Parameter setting & configuration
Parameterisable function blocks
182 L EDS94TA11010xxxx EN 1.2 - 03/2010
3.21 Parameterisable function blocks
This subchapter lists all relevant parameterisable function blocks of the technology
application in alphabetical order with the corresponding parameters.
3.21.1 Adaption_Positioncontroller
3.21.2 Adaption_Speedcontroller
is ans instance of Function
L_TbCurve Adaption of the position controller by characteristic or curve function y = f(x)
Parameter Possible settings Information
C04103 Characteristic mode
0 Entire range
1 Symmetrical to the Y axis Lenze setting
2 Symmetrical to the zero point
C04104/1...9 -200.00 % 200.00 x value of the characteristic function
Subcode 1 ... 9 corresponding to
the support point values X1 ... X9.
C04105/1...9 -200.00 % 200.00 y value of the characteristic function
Subcode 1 ... 9 corresponding to
the support point values Y1 ... Y9.
is ans instance of Function
L_TbCurve Adaption of the speed controller by the characterstic or curve function y = f(x)
Parameter Possible settings Information
C04100 Characteristic mode
0 Entire range
1 Symmetrical to the Y axis Lenze setting
2 Symmetrical to the zero point
C04101/1...9 -200.00 % 200.00 x value of the characteristic function
Subcode 1 ... 9 corresponding to
the support point values X1 ... X9.
C04102/1...9 -200.00 % 200.00 y value of the characteristic function
Subcode 1 ... 9 corresponding to
the support point values Y1 ... Y9.
Vue de la page 181
1 2 ... 177 178 179 180 181 182 183 184 185 186 187 ... 231 232

Commentaires sur ces manuels

Pas de commentaire