8 Commissioning of the CANopen Logic bus
8.11 Preparing the restart
61
Lenze · Controller-based Automation · CANopen® Communication Manual · DMS 6.3 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8.11.3 Special features of the I/O system 1000 (EPM-Sxxx)
There are different possibilities for restarting the I/O system:
Automatically
Automatically with factory adjustment
Using the »Engineer«
For the corresponding settings, first tick the "Expert settings" on the CANopen Remote Device tab.
8.11.3.1 Automatic restart
Settings for automatic initialisation by the Lenze Controller:
1. Enter all desired parameter values under the All parameters tab.
2. Tick "Create all SDOs" under the CANopen Remote Device tab.
When the I/O system has been replaced
1. Set the node address and the baud rate at the code switch.
2. Start the Lenze Controller..