Establishing an online connection
Going online
80
Lenze · Engineer · 2.13 EN - 10/2014
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Ethernet / Ethernet IPC
( 83)
PROFIBUS
( 84)
PROFINET
( 85)
Gateway controller -> CAN ( 85)
Gateway controller -> EtherCAT
( 86)
Gateway Controller -> EtherCAT ADS (Beckhoff)
( 87)
Gateway Siemens - STEP 7 Communication Server (available by call in STEP 7) ( 89)
6.2.1.1 Diagnostic adapter
For commissioning and diagnostics of a controller of the Inverter Drives 8400 and Servo Drives 9400
series you can e.g. use the diagnostic adapter offered by Lenze:
[6-2] Example of a connection via diagnostic adapter between an Engineering PC and a 9400 HighLine.
Tip!
Via the menu command OnlineStatus of diagnostic adapter, you can have the operating
status of the diagnostic adapters connected to the Engineering PC displayed.
Preconditions:
The diagnostic adapter is connected to the diagnostic interface X6 at the controller and to a free
USB port at the (Engineering) PC.
The driver required for the diagnostic adapter is installed.
The control electronics of the controller is supplied via the X2 plug with 24-V low voltage.
How to configure an online connection via the diagnostic adapter:
1. Go to the Communication path dialog box and select "Diagnostic adapter" from the Bus
connection list field.
The following step is only required if several diagnostic adapters are connected to the PC:
Note!
Observe the documentation supplied with the diagnostic adapter!
The online connection to the diagnostic adapter is a 1:1 connection.