Wiring of the standard device
Basics for wiring according to EMC
Wiring outside of the control cabinet
5
5.3
5.3.6
5.3−5
EDSVS9332P EN 5.0−07/2013
5.3.6 Wiring outside of the control cabinet
Notes for cable routing outside the control cabinet:
ƒ The longer the cables the greater the space between the cables must
be.
ƒ If cables for different signal types are routed in parallel, the
interferences can be minimized by means of a metal barrier or
separated cable ducts.
Cover
Barrier without
opening
Power cables
Signal cables
EMVallg001
Fig. 5.3−3 Cable routing in the cable duct with barrier
Cover
Communication cables
Cableduct
Measuring cables
Analog cables
Control cables
Power cables
EMVallg002
Fig. 5.3−4 Cable routing in separated cable ducts