Lenze EVS9332xP Manuel d'utilisateur Page 113

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 445
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 112
Wiring of the standard device
Standard devices in the power range 15 ... 30 kW
Motor connection
5
5.5
5.5.6
5.5−9
EDSVS9332P EN 5.0−07/2013
PE
PE
T1
T1
T2
T2
U
VW
4
4
T1
T2
2.5 Nm
22,1 lb-in
T1
T2
2.5 Nm
22,1 lb-in
}
+
PE
}
+
PE
0
0
1
1
3
2
2

U, V, W,
PE
5 Nm
44 lb-in
M 6
9300std030
Fig. 5.5−5 Motor connection with PTC thermistor or thermal contact (NC contact)
Motor connection with Lenze system cable with integrated control
cable for the motor temperature monitoring
Shield sheet
Clamp entire shield and shield of the control cable for the motor
temperature monitoring with the straps. If required, fix by means of
cable tie.
Motor cable connection and separate control cable for the motor
temperature monitoring
Shield sheet
Clamp shield of the motor cable and shield of the cable for the motor
temperature monitoring with the straps. If required, fix by means of
cable tie.
PE stud
PE cable connection with ring cable lug
U, V, W
Motor cable connection
Check the correct polarity. Observe maximum length of the motor cable.
Max. connectable cable cross−section: 50 mm
2
with ring cable lug
T1, T2 for motor temperature monitoring
Cable connection for PTC thermistors or thermal contacts (NC contacts)
Vue de la page 112