Function library
Function blocks
3.5.12 BCD decade switch (BCD)
3−126
l
EDSVS9332P−EXT DE 2.0
With handshaking, minimum wiring
Set BCD mode = 1.
BCD_C
B C D x - N E W - D A T A
t
B C D x - D A T A x
B C D x - R E A D
2 n d c y c l e 3 r d c y c l e 1 s t c y c l e1 s t c y c l e
( 4 i n p u t s )
( I n p u t )
( O u t p u t )
Fig. 3−79 Sequence of handshaking
Function
l The superimposed control (e.g. PLC) determines the time of data transmission.
l After the acceptance signal has been sent from the control to BCDx−READ the BCD is read.
The signal must be sent for every BCD.
The reading routine of the FB BCD remains in waiting position until the data transmission is
started.
The BCDs are read in the following sequence:
1. Sign
2. BCD 1
3. BCD 2
4. etc.
Transmission sequence of a BCD:
Input/output Signal Function
BCDx−DATA1 ...
BCDx−DATA4
Generating data for the first or next BCD via PLC.
BCDx−NEW−DATA HIGH Enables the transmission for the next BCD.
BCDx−READ LOW−HIGH edge Reading of the BCD data to the FB BCD.
BCDx−NEW−DATA LOW Inhibits the transmission for the next BCD.
BCDx−READ LOW Set via PLC.