Opening the Application Sample
Going online
20
Lenze · Servo Inverter i700 | Application Sample · DMS 1.0 EN - 09/2012 - TD11
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3 Going online
To establish an online connection to the Controller, the communication settings (Set Active Path)
must be adapted first. Setting up communication to the Controller
( 9)
6.3.1 Transferring the project to the control system - "logging in"
The "Login" command transfers the PLC program to the Controller.
Transfer the project to the Controller by "logging in" to the control system:
Menu command Online Login
6.4 Loading and starting the PLC program
Select the OnlineLoad menu command to load the PLC program to the Controller.
Select the OnlineRun menu command to start the PLC program.
Alternatively, execute the DebugRun menu command or press <F5>.
Tip!
If the project is to be loaded automatically after a restart of the device, you can install it
as "Boot project".
How to install the project as boot project:
1. Select the OnlineCreate boot application for L-force Controller menu command.