Function library
Working with function blocks
3.1.3 Connecting function blocks
3−8
l
EDSVS9332S−EXT EN 2.0
Create connections
1. Determine the signal source for ARIT2−IN1:
Change to the code level using the arrow keys
Select C0601/1 using or .
Change to the parameter level using PRG.
Select output AIN2−OUT (selection number 55) using or .
Confirm using SH + PRG
Change to the code level again using PRG.
2. Determine signal source for ARIT2−IN2:
Select C0601/2 using .
Change to the parameter level using PRG.
Select output AIN2−OUT (selection number 55) using or .
Confirm using SH + PRG
Change to the code level again using PRG.
3. Parameterise ARIT2:
Select C0600 using .
Change to the parameter level using PRG.
Select multiplication (selection number 3).
Confirm using SH + PRG
Change to the code level again using PRG.
4. Determine signal source for AOUT1:
Select C0431 using .
Change to the parameter level using PRG.
Select output ARIT2−OUT (selection number 5505).
Confirm using SH + PRG
Change to the code level again using PRG.
5. Enter function block ARIT2 in the processing table:
Select C0465 and subcode 8 using .
Change to the parameter level using PRG.
Enter function block ARIT2 (selection number 5505).
Confirm using SH + PRG
Change to the code level again using PRG.
The sequence of the FB processing is thus determined.