13 Error messages
13.2 Possible causes and remedies
90
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Profibus watchdog: Monitoring time elapsed [0x00c88130]
Profibus: Data_Exchange state exited [0x00c88131]
Profibus watchdog: DP-V1 MSAC2 elapsed [0x00c88132]
Response (Lenze setting printed in bold) Setting: C13880/1 / C14880/1 (; Adjustable response)
: None System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause Remedy
Permanent interruption of communication to the
PROFIBUS master.
See also chapter "Permanent interruption of PROFIBUS
communication" ( 78).
Check cables and terminals.
Response (Lenze setting printed in bold) Setting: C13880/1 / C14880/1 (; Configurable response)
: None System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause Remedy
Data exchange via PROFIBUS has been terminated.
See also chapter "Permanent interruption of PROFIBUS
communication" ( 78).
Check cables and terminals.
The slave must receive new parameterisation and
configuration files from the master in order to be able to
exchange data again.
Response (Lenze setting printed in bold) Setting: C13880/2 / C14880/2 (; Configurable response)
: None System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause Remedy
Permanent interruption of communication to C2-
PROFIBUS master.
See also chapter "Permanent interruption of PROFIBUS
communication" ( 78).
Check cables and terminals.