Lenze PC-based Automation Industrial PC Manuel d'utilisateur Page 175

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 226
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 174
2.5 EN - 01/2012 L 175
Industrial PC | Parameter setting & configuration
Parameter reference
Industrial PC extension modules
C1081/3
C1081/4
C1081/5
Parameter | Name:
C1081/3 | ECAT master in requested state
Data type: UNSIGNED_8
Index: 23494.3
d
=
0x5BC6.0x03
h
Normally, the state is requested by the PLC. For possible requested states see C1080/1 ( 174).
Value "0": Master is not in a requested state.
Value "1": Master is in a requested state.
Display range (min. value | unit | max. value)
0 1
; Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1081/4 | ECAT slaves in requested state
Data type: UNSIGNED_8
Index: 23494.4
d
=
0x5BC6.0x04
h
Value "0": One or more slaves differ from the state requested by the master.
Value "1": All slaves have the state requested by the master.
Display range (min. value | unit | max. value)
0 1
; Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1081/5 | ECAT master: State information
Data type: UNSIGNED_32
Index: 23494.5
d
=
0x5BC6.0x05
h
Display of additional information on the current state of the master
The bits are set to value 1 if the respective states are reached.
Vue de la page 174
1 2 ... 170 171 172 173 174 175 176 177 178 179 180 ... 225 226

Commentaires sur ces manuels

Pas de commentaire