Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05 175
7 CiA402 device profile
7.4 Device control
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7.4.1.4 Activate quick stop
From all states
Power section inhibited (pulse inhibit)
Power section enabled
This command serves to activate quick stop
when operation is enabled.
• Irrespective of the setpoint specified, the
drive is brought to a standstill with the
deceleration set for quick stop (0x6085
or
0x6885
for axis B).
• A changeover to the "Quick stop is active
"
device status takes place.
If the operation has not been enabled yet
(status "Ready to switch on
" or "Switched on"),
this command triggers a change to the "Switch
on disabled" device status.
Bit pattern for the "Quick stop" in the Controlword (0x6040 or 0x6840 for axis B):
Bits 15 - 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Fault reset Control bits depending on the operating mode Enable
operation
Activate quick
stop
Enable voltage Switch on
X0X X XX01X
Note!
During quick stop, the drive executes the setpoint generation and no longer follows the
setpoint defined by the controller!
If several drives execute a chained synchronous motion, the quick stop function has to
be coordinated by the Controller by means of a quick stop profile (master function). In
this case, quick stop cannot be activated via the control bit 6!
1
2
0
Ready to
switch on
Not ready to
switch on
Switched
on
Operation
enabled
Fault reaction
active
Fault
Switch-on
disabled
Quick stop
active
Power-on