8.5 System error messages
Drive PLC
Appendix
8−8
L
DrivePLC DE 6.0
8.5.1 Overview of system error messages, error sources and reactions
System error message Possible settings/response
Lenze setting ü setting possible
Available in
No. Display Source Meaning
Code TRIP Message Warning FAIL−
QSP
Off Drive
PLC
Servo
PLC
ECSxA
x011 OC1 MCTRL Motor cable short circuit ü ü
x012 OC2 MCTRL Motor cable earth fault ü ü
x015 OC5 MCTRL I x t overload ü ü
x016 OC6 MCTRL I
2
x t overload (C0120) ü
x017 OC7 MCTRL I x t warning (C0123) C0604 ü ü ü
x018 OC8 MCTRL I
2
x t warning (C0127) C0605 ü ü ü
x020 OU MCTRL Overvoltage in the DC bus ü ü
x030 LU MCTRL Undervoltage in the DC bus ü ü
x032 LP1 MCTRL Motor phase failure C0597 ü ü ü ü
x050 OH MCTRL Heat sink temperature higher than fixed limit
temperature
ü ü
x051 OH1 MCTRL Temperature inside the controller > 90° C ü
x053 OH3 MCTRL Motor temperature higher than fixed limit tem-
perature
C0583 ü ü ü
x054 OH4 MCTRL Heat sink temperature higher than variable li-
mit temperature (C0122)
C0582 ü ü ü
x055 OH5 MCTRL Temperature inside the controller > C0124 C0605 ü ü ü
x057 OH7 MCTRL Motor temperature higher than variable limit
temperature (C0121)
C0584 ü ü ü
x058 OH8 MCTRL Motor temperature via inputs T1/T2 too high C0585 ü ü ü ü
x061 CE0 AIF Communication error between AIF mo-
duleóPLC
C0126 ü ü ü ü ü
CAN communication error:
x062 CE1 CAN1 CAN1_IN (monitoring time can be set under
C0357/1)
C0591
ü ü ü ü ü
x063 CE2 CAN2 CAN2_IN (monitoring time can be set under
C0357/2)
C0592
x064 CE3 CAN3 CAN3_IN (monitoring time can be set under
C0357/3)
C0593
x065 CE4 CAN CAN BUS−OFF status
(too many faulty telegrams received)
C0595 ü ü ü ü ü
x066 CE5 CAN CAN time−out (gateway function C0370) C0603 ü ü ü ü ü
x070 U15 internal Undervoltage of internal 15 V voltage supply ü ü ü
x071 CCr internal Internal error
1)
ü ü ü
x072 PR1 internal Check sum error in parameter set 1 ü ü ü
x074 PEr internal Program error
1)
ü ü ü
x075 PR0 internal General error in the parameter sets
1)
ü ü ü
x076 PR5 internal Error saving parameters ü ü
x079 PI internal Error during parameter initialisation
1)
ü ü ü
x080 PR6 internal Too many user codes ü ü ü
x082 Sd2 MCTRL Resolver error C0586 ü ü ü ü
x083 Sd3 MCTRL Encoder error at X9 PIN 8 C0587 ü ü ü
x085 Sd5 MCTRL Encoder error at analog input (X6) (C0034 = 1) C0598 ü ü ü ü
x086 Sd6 MCTRL Sensor error: motor temperature (X7 or X8) C0594 ü ü ü ü
x087 Sd7 MCTRL Absolute−value encoder error at X8
1)
C0025 ü ü
x088 Sd8 MCTRL Absolute−value encoder error at X8
1)
C0580 ü ü ü
x: 0 = TRIP, 1 = Message, 2 = Warning, 3 = FAIL−QSP
1)
After error correction: completely deenergise the device!