5.8 L_IOSSIDataToIO − Counter function
Function library LenzeIOSystem.lib
Function blocks
5−16
L
LenzeIOSystem.lib EN 1.7
5.8 L_IOSSIDataToIO − Counter function
Depending on a comparison value, the two outputs of the module can be set via function block
L_IOSSIDataToIO.
To the outputs, different comparison functions or comparison values can be assigned, which must
be transferred to the SSI module in succession.
L_IOSSIDataToIO
dwSet_Compare
abyPDO_DataToIO
Converter
dw to byte
Byte
0
DI
Byte
2
DI
Byte
3
DI
Byte
1
DI
bControl_SetOut_1
bControl_SetOut_0
bControl_Condition
ð Inputs (Variable type: VAR_INPUT)
Variable name Data type Information/possible settings
bControl_Set_0 Bool Output 0
Monitor comparison value
0 Off
1 On
bControl_Set_1 Bool Output 1
Monitor comparison value
0 Off
1 On
bControl_Condition Bool Set condition of outputs
0 Actual value > comparison value
1 Actual value < comparison value
dwSet_Compare Double word Enter comparison value
Outputs ð (Variable type: VAR_OUTPUT)
Identifier Data type Value/meaning
abyPDO_DataToIO Byte array Interface with the inputs of function blocks L_IOPDO15 or L_IOPDO610 for the
transfer of information from the counter module.