4.6 L_IOParCounterModule − Counter function
Function library LenzeIOSystem.lib
Function blocks
4−14
L
LenzeIOSystem.lib EN 1.7
4.6 L_IOParCounterModule − Counter function
The counter modules are parameterised via function block L_IOParCounterModule.
· The counter function is specified via inputs byFunction_CH1 and byFunction_CH2.
L_IOParCounterModule
bExecute
nState
byFunction_CH2
byFunction_CH1
byAnalogModuleNr
byNodeAdr
CTRL
EPM-T110
Ixxxh
ð Inputs (Variable type: VAR_INPUT)
Variable name Data type Information/possible settings
bExecute Bool Execute write request
FALSE ä TRUE Write request is executed
byNodeAdr Byte Device address: 1 − 63
byAnalogModuleNo Byte Slot number
· The first analog module installed is assigned slot number 1.
· A maximum of 16 analog modules may be plugged.
byFunction_CH1 Byte Parameterise function
Default (2 * 32 bit counters) function code 00
h
^ 6−10
byFunction_CH2 Byte Parameterise function
Default (2 * 32 bit counters) function code 00
h
^ 6−10