6 Commissioning of the PROFINET
6.2 The commissioning steps in detail
30
Lenze · Controller-based Automation · PROFINET® Communication Manual · DMS 1.2 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4. Select the I/O modules to be used for the I/O device in the "Add device" dialog window
and add it to the I/O device by using the Add device button.
5. Repeat the steps 1. ... 4. for further Lenze Controllers connected to the PROFINET.
Note!
The I/O modules defined by Lenze behave consistently.
If the value of a consistent module changes, the entire module is written on the bus in
the same cycle.
In order to guarantee consistent data between master and slave, make sure that the
master supports consistent modules as well.