L DMS 4.0 EN - 07/2007 37
L-force Loader
Appendix
Error numbers, causes & remedies
C300h Error while downloading the DDS binary file. Repeat the download.
If the problem still occurs, contact the Lenze
Hotline.
C301h The target system found on the bus does not
correspond to the target system for which
the DDS binary file has been created.
Check the device address or select a different
DDS binary file.
C302h The project on the target system is a newer
version than the project to be loaded.
C303h Downloading of the DDS binary file has been
cancelled.
Repeat the download.
If the problem still occurs, contact the Lenze
Hotline.
C304h Internal program error
(PLC program buffer cannot be created.)
Restart the program.
If the problem still occurs, contact the Lenze
Hotline.
C400h The device description assigned to the GDC
parameter set file cannot be found.
Check the settings for the GDC search path in
the initialisation file (key "SearchPathPDB").
If the problem still occurs, contact the person
who created the GDC parameter set file.
C401h Internal program error.
(Transfer list not yet created.)
Restart the program.
If the problem still occurs, contact the Lenze
Hotline.
C402h The maximum permissible number of errors
has been exceeded during the parameter
transfer.
Repeat the parameter transfer.
If necessary, increase the number of
permissible errors in the initialisation file
(key "MaxTransferErrors").
C403h The preparations for the parameter transfer
have failed.
Restart the program.
If the problem still occurs, contact the Lenze
Hotline.
C404h The device description does not correspond
to the target system found on the bus.
Check the device address. If the device
description has been loaded manually, select
a different device description. Otherwise,
select a different GDC parameter set file.
C405h Internal program error.
(Transfer list cannot be created.)
Restart the program.
If the problem still occurs, contact the Lenze
Hotline.
C406h The "pdb.ini" file cannot be read. Check that the "pdb.ini" file is in the »L-force
Loader« program directory. If you cannot find
it in the directory, reinstall the »L-force
Loader«.
C407h The GDC parameter set file has been created
for a newer device version than that found
on the bus.
Create a new GDC parameter set file for the
device version present on the bus.
C500h Faulty script file (communication parameters
cannot be read).
Check the script file, especially the
[Communication] section.
C501h Error while creating the log file. Check the log file name entered in the
command line and try again.
C502h Error while opening the script file. Check the script file name entered in the
command line and try again.
C503h Error while opening the DDS binary file. Check the name of the target system causing
the error (e.g. "DEVICE001") in the log file and
the specifications in the script file.
C504h Error while opening the GDC parameter set
file.
C600h No connection to the target system. Check the wiring between PC and target
system.
Restart the program.
C601h The target system cannot be identified. Contact the Lenze Hotline.