DMS 2.2 EN 07/2011 TD17 L 29
Control technology | PROFIBUS communication manual
Commissioning of PROFIBUS
Detailed commissioning steps
6.2.6.2 Configuring the PROFIBUS master
How to configure the PROFIBUS master:
1. Add the bus interface to the PLC configuration:
The "ProfibusMaster" subelement represents the PROFIBUS interface of the IPC to
which the logic bus is connected.
2. Set DP parameters for the PROFIBUS master:
The standard setting of the PROFIBUS master station address is ’1’. Only change
the setting if the address is to deviate from ’1’.
The "highest station address" is incremented automatically with each added
slave. Thus the value should not be changed manually.
•The GSE file... button serves to open and inspect the device-related GSE file.
•The Groups... button leads to the Group properties dialog. The group properties
refer to the slaves assigned to the master.