Lenze MC-CAN2 Manuel d'utilisateur Page 30

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 32
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 29
5 Electrical installation
LDCDS−MC−CAN2 DE/EN 3.0
30
H1_E_INST−Hin_Treiber−Install
Specification of the transmission cable
We recommend the use of CAN cables in accordance with ISO 11898−2:
CAN cable in accordance with ISO 11898−2
Cable type Paired with shielding
Impedance
120 W (95 ... 140 W)
Cable resistance/cross−section
Cable length £ 300 m £ 70 mW/m / 0.25  0.34 mm
2
(AWG22)
Cable length 301  1000 m
£ 40 mW/m / 0.5 mm
2
(AWG20)
Signal propagation delay
£ 5 ns/m
Note!
For commissioning the unit, the corresponding driver has to be installed on the
Industrial PC. It can be found on the DVD from the scope of supply of the
standard device ("PC−based automation" or "Controller−based automation").