Lenze EPM−T9XX Modular system Manuel d'utilisateur Page 488

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 544
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 487
Parameterising 2/4xcounter module
Encoder with GATE (modes 36 ... 38)
13
Parameter setting via PROFIBUS−DP
13.2
13.2.19
L
13.2−54
EDSPM−TXXX−9.0−11/2009
The counter is incremented by 1 on
l a LOW−HIGH edge at input IN2 / IN5 (A) and a LOW level at the input
IN3 / IN6 (B).
l a HIGH−LOW edge (track A) at input IN2 / IN5 (A) and a HIGH level at input
IN3 / IN6 (B).
epm−t168
Fig. 13.2−75 Signal characteristic of 2/4xcounter in the mode 37 (upcounter)
The counter is decremented by 1 on
l a LOW−HIGH edge at input IN2 / IN5 (A) and a HIGH level at input
IN3 / IN6 (B).
l a HIGH−LOW edge at input IN2 / IN5 (A) and a LOW level at the input
IN3 / IN6 (B).
epm−t169
Fig. 13.2−76 Signal characteristic of 2/4xcounter in the mode 37 (downcounter)
Signal characteristic in mode 37
Vue de la page 487
1 2 ... 483 484 485 486 487 488 489 490 491 492 493 ... 543 544

Commentaires sur ces manuels

Pas de commentaire