6 Technical data
General data and operating conditions
EDKMF2133 DE/EN/FR 6.1
66
H1_Daten−protokollDat
6 Technical data
General data and operating conditions
Communication−relevant data Values
Communication media RS 485
Network topology without repeater: line / with repeater: line or tree
Number of devices Standard: 32 (= 1 bus segment) / with repeaters: 125
Cable length / segment 1200 m
(depending on the baud rate and the cable type used)
Communication profile PROFIBUS−DP
(DIN 19245 part 1 and part 3)
PUO ID number 2133
hex
Drive profile
l DRIVECOM profile "Power Transmission 20", can be switched off
l PROFIDRIVE version 2, can be switched off
(status machine and PIV interface)
PROFIBUS participants Slave
Baud rate for cable type A (EN
50170)
9.6 kbits/s up to 12 Mbits/s (automatically detected)
Process data words (PCD),
16bits
1 word ... 12 words
DP user data length Parameter data channel (4 words) +
process data words (1 .... 12 words)
External voltage supply Values
"+" V = 24VDC (21.6 V − 0% ... 26.4 V + 0 %)
I = 120 mA
"−" Reference potential for external voltage supply
Operating conditions Values Deviations from standard
Climatic conditions
Storage 1 K3 to IEC/EN 60721−3−1 −25 °C ... + 60 °C
Transport 2 K3 to IEC/EN 60721−3−2
Operation 3 K3 to IEC/EN 60721−3−3 0 °C ... + 55 °C
Enclosure IP20
Degree of pollution 2 to IEC/EN 61800−5−1
Vue de la page 65