Mechanical installation
Important notes
4
17
EDBCSXKXXX EN 1.0
4 Mechanical installation
4.1 Important notes
ƒ ECSxKxxx capacitor modules are provided with IP20 protection and can therefore
only be used for installation into control cabinets.
For thermally separated mounting (ECSDKxxx): IP54 o n the heatsink side
ƒ If the cooling air contains air pollutants (dust, fluff, grease, aggressive gases):
Take suitable preventive measures , e.g. separate air duct, installation of filters,
regular cleaning.
ƒ Ensure free space!
Ensure unimpeded ventilation of cooling air and outlet of exhaust air.
You can install several capacitor modules next to each other without any clearance
in a control cabinet.
Allow a free space of 50 mm above and below other installations or limitations.
ƒ The mounting plate of the control cabinet must be electrically conductive.
ƒ In case of continuous vibrations or shocks use shock absorbers.
Possible mounting positions
Vertically on the m ounting plate with DC-bus connections at the top
Mounting techniques
ƒ With fixing rails (standard,  18)
ƒ Thermal separation (”push-through technique”, 19)
ƒ In ”cold plate” technique ( 21)