Lenze EMZ9374IB Manuel d'utilisateur Page 59

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 122
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 58
Commissioning
Configuration with internal DIP switches
Settings in the programming mode
7
l
59
EDBMZ9374X DE/EN/FR 4.2
7.3.1 Settings in the programming mode
Digital inputs and outputs (terminals I/O1 ... I/O8) are configured in the
programming mode .
DIP switch assignment in the programming mode
DIP switches Function Setting notes Note
1 Terminal I/O1
Set the DIP switches according to the
terminal assignment I/O1 ... I/O8:
l DIP switches ON: Terminal
configured as output
l DIP switches OFF: Terminal
configured as input
An error message is
displayed (LED
ERROR" on), if a
terminal is configured
as output and a HIGH
level is applied.
2 Terminal I/O2
3 Terminal I/O3
4 Terminal I/O4
5 Terminal I/O5
6 Terminal I/O6
7 Terminal I/O7
8 Terminal I/O8
9 Set DIP switch to OFF
10 Set DIP switch to OFF
11 Set DIP switch to OFF
12 Programming
mode /
Operating
mode
Set DIP switch to ON
(Programming mode)
In the programming
mode
l LED
ERROR module" is
flashing
l LED
Operation" is off
Setting sequence:
1. Switch on the power supply for the terminal extension.
2. Set DIP switch 12 to ON (programming mode).
3. Configure the terminals I/O1 ... I/O8 using DIP switches 1 ... 8.
4. Set DIP switch 12 to OFF (operating mode).
The configuration of the inputs/outputs is completed.
5. Switch off the power supply for the terminal extension.
The programming mode is quit only after the power supply has benn
switched off.
Vue de la page 58
1 2 ... 54 55 56 57 58 59 60 61 62 63 64 ... 121 122

Commentaires sur ces manuels

Pas de commentaire