Technical data
Protocol data
7
Feldbus-Baugruppe 2113 INTERBUS
7.3
7.3.3
L
7.3-3
EDSIBS-1.0-06/2003
7.3.3 Protocol data
Field Values
Maximum number of controllers
Dependent on INTERBUS master (e.g. Phoenix Contact G4-Master).
For the following data, always the smaller value applies dependent on the
fact, whether PCP communication is available or not:
With PCP communication:
Wit hout PCP communication:
62 or
256/number PD
Process data words (PD) 1 ... 10 (selectable) Default setting: 2 words
Parameter data words (PCP) 0, 1, 2, 4 Default setting: 1 word
Maximum number of data words As a maximum the data word sum (PD + PCP) is to amount to 10 words.
INTERBUS ID (module ID)
Module ID for set length
(
)
3
dec
=03
hex
PCP 0 words
227
dec
=E3
hex
PCP 1 word
224
dec
=E0
hex
PCP 2 words
225
dec
=E1
hex
PCP 4 words
Maximum PDU length 64 byte
Supported PCP services Initiate, abort, status, identify, Get-0V-long, read, write